| Sign In | Join Free | My ecer.co.uk | 
              
  | 
      
Brand Name : MTL
Model Number : TP48-3-N-NDI
Certification : CE
Place of Origin : USA
MOQ : 1 piece
Price : negotiable
Payment Terms : T/T
Supply Ability : 100pcs per month
Delivery Time : on request
Packaging Details : standard carton packing
Leakage current : Less than 1µA at max. working voltage
Electrical Safety : To BS EN 61643-21 for surge protection devices
Ambient temperature : -40°C to +85°C (-40°F to +185°F) (working) -40°C to +85°C (-40°F to +185°F) (storage)
Humidity : 5% to 95% RH (non-condensing)
Bandwidth : 1MHz
Weight : 175g. (6.2oz.)
The TP48 range of surge protection devices uniquely provide a level of protection for 2, 3 and 4 wire field-mounted transmitters that is far in excess of the optional transient protection facilities available from the transmitter manufacturers - without involving any additional wiring, conduit modifications or other expensive extras.
 The TP48 range protection network consists of high-power, solid state electronics and a gas-filled discharge tube capable of diverting 20kA impulses. The whole unit is encased in a 316 stainless steel housing, threaded for the common conduit entries used on process transmitters. Versions are available for 1/2” NPT, 20mm ISO, and G1/2” (BSP 1/2 inch) threaded entries.
SPECIFICATION
Maximum surge current:20kA peak current (8/20µs waveform)
Leakage current:Less than 1µA at max. working voltage
Working voltage:35V dc maximum
Bandwidth:1MHz
Resistance:No resistance introduced into loop
Ambient temperature limits:-40°C to +85°C(-40°F to +185°F) (working);-40°C to +85°C(-40°F to +185°F) (storage)
Humidity:5% to 95% RH (non-condensing)
Electrical connections:TP48,3 flying leads (line1, line 2 & earth) ;TP48 3 Wire,4 flying leads (+ve, -ve, signal & earth)
;TP48 4 Wire,5 flying leads (+ve, -ve, signal +ve, signal -ve, earth);Wire size: 32/0.2 (1.0mm2, 18 AWG) Lead length: 250mm (minimum)
Casing:316 stainless steel suitable for harsh environments
Threads:TP48-3-N & TP48-4-N - 1/2”NPT TP48-3-I & TP48-4-1 - 20mm ISO ) (M20 x 1.5);TP48-3-G & TP48-4-G - G 1/2”(BSP 1/2”)
Weight:175g. (6.2oz.)
Dimensions:See figure 1
EMC compliance:To Generic Immunity Standards;BS EN 61326-1 for industrial environments
Hazardous Area:Ex ia IIC T4, Ceq=O, Leq=0; the unit can be connected without further,certification into any intrinsically safe loop with open circuit voltage <60V and input power <1.2W.Ex d IIC T4; the unit is apparatus approved to flameproof (explosion- proof) standards, and can be fitted into a similarly approved housing.
 Electrical Safety:To BS EN 61643-21 for surge protection devices
Related Part Number:
|  			 HCU16  |  			 			 MTL5521  |  			 			 MTL4546Y  |  			 			 MTL7761PAC  |  		
|  			 HCU3700  |  			 			 MTL5522  |  			 			 MTL4549Y  |  			 			 MTL7765AC  |  		
|  			 HM64RIB20-1.0  |  			 			 MTL5531  |  			 			 MTL4573  |  			 			 MTL7787+  |  		
|  			 HM64RIB20-1.5  |  			 			 MTL5532  |  			 			 MTL4575  |  			 			 MTL7787P+  |  		
|  			 HMM64  |  			 			 MTL5541  |  			 			 MTL4646Y  |  			 			 MTLCPS16  |  		
|  			 HMRIB16-1.0  |  			 			 MTL5541S  |  			 			 MTL4850  |  			 			 NJ5-18GK-N  |  		
|  			 HMS64  |  			 			 MTL5544  |  			 			 MTL4851  |  			 			 SD150X  |  		
|  			 HTP-SC32  |  			 			 MTL5544D  |  			 			 MTL4852  |  			 			 SD32  |  		
|  			 MTL4044D  |  			 			 MTL5546  |  			 			 MTL5018  |  			 			 SD32X  |  		
|  			 MTL4511  |  			 			 MTL5546Y  |  			 			 MTL5032  |  			 			 SDRTD  |  		
|  			 MTL4516  |  			 			 MTL5561  |  			 			 MTL5042  |  			 			 SLP32D  |  		
|  			 MTL4516C  |  			 			 MTL5573  |  			 			 MTL5044  |  			 			 TP48-3-I-NDI  |  		
|  			 MTL4521  |  			 			 MTL5575  |  			 			 MTL5049  |  			 			 TP48-3-N-NDI  |  		
|  			 MTL4541  |  			 			 MTL5582B  |  			 			 MTL5511  |  			 			 TP48-4-I-NDI  |  		
|  			 PCL45USB  |  			 			 MTL7728+  |  			 			 MTL5514D  |  			 			 TP48-4-N-NDI  |  		
|  			 MTL4544  |  			 			 MTL7756AC  |  			 			 MTL5516  |  			 			 TP48-N-NDI  |  		
|  			 MTL4544D  |  			 			 MTL7760AC  |  			 			 MTL5516C  |  			 			 ZB24571  |  		

| 
                                             | 
                
                        USA EN 61643-21 MTL Safety Barrier TP48-3-N-NDI Images |